ClaveQ
Private beta · by invitation

OT, ICS & SCADA encryption

Find out which of your OT connections carry traffic in clear text.

Most industrial protocols were designed for closed networks and carry commands and readings unencrypted. Protected versions exist, such as Modbus/TCP Security and DNP3 Secure Authentication, but both ends have to support them and someone has to switch them on. ClaveQ works from a mirror port and touches no device. Connection by connection, it tells you which ones can be trusted and which cannot.

No agents. No decryption. Zero packets sent onto the monitored network.

Why it matters

Unencrypted is only half the question.

Today · clear text

Commands anyone can read, and often forge

Anyone with access to the network segment can read a clear-text control protocol, and can often replay or alter it. So the first job is to list the connections that carry no protection.

Tomorrow · quantum

Encrypted is not the same as quantum-safe

Connections encrypted today mostly rely on public-key cryptography that a quantum computer would break. ClaveQ rates each one: what is protected now, and what will need migrating.

Post-quantum migration

Frameworks · evidence

Evidence for your assessments

Findings map to IEC 62443, NERC CIP (North America), CNSA 2.0 and the EU Cyber Resilience Act. ClaveQ sets migration phases against the NCSC timeline and exports the findings as a CycloneDX CBOM.

What is a CBOM?

The protocols

Modbus, DNP3, OPC UA and more — down to the protection in use.

For each connection ClaveQ records the protocol, whether it is protected, and how. Where a protocol's security settings are themselves encrypted, or otherwise not visible on the wire, ClaveQ says so rather than guessing.

ProtocolWhere you find itProtected by default?Optional protection (add-on)
Modbus/TCPPLCs, RTUs and meters across water, energy and manufacturingNoModbus/TCP Security adds TLS, on port 802.
DNP3Telemetry between a SCADA master and outstations in water and electricity, including serial links bridged onto TCPNoSecure Authentication adds message authentication, but the traffic stays readable.
OPC UAData exchange between controllers, HMIs, historians and business systemsDepends on modeBuilt in, not an add-on: Sign or SignAndEncrypt mode. Set to None, it offers no protection.
S7comm / S7comm-Plus (Siemens)Siemens S7 controllers and their engineering and HMI stationsS7comm: No. S7comm-Plus: not stated on this pageS7comm-Plus on S7-1200/1500 adds integrity protection; recent firmware on both can use TLS.
EtherNet/IP (CIP)Rockwell and other factory and process controllersNoCIP Security adds TLS, and DTLS for real-time I/O.
IEC 60870-5-104Electricity grid telecontrolNoIEC 62351 adds TLS and authentication.
IEC 61850 (MMS, GOOSE, Sampled Values)Substation automation and protectionNoIEC 62351 adds TLS for MMS and message authentication for GOOSE and Sampled Values.
IEEE C37.118 (synchrophasor)Phasor measurement units reporting grid conditions to control centresNoThe standard treats security as out of scope, so it relies on protection around it, such as a VPN or IPsec.
BACnet/IPBuilding systems: heating and ventilation, lighting, access controlNoBACnet Secure Connect (BACnet/SC), a separate secure transport, adds TLS.
GE-SRTPGE (now Emerson) PACSystems and Series 90 controllersNo. Newer firmware protects the log-on only.Commands and data that follow the log-on are neither encrypted nor authenticated.
MQTTTelemetry from sites and devices to brokers and cloud platformsNoTLS, usually on port 8883.
SNMP v1, v2c, v3Monitoring of switches, routers and other network devicesv1 and v2c: No. v3: depends on configuration.v3 adds authentication and, where configured, encryption. v1 and v2c send their shared password (“community string”) in clear text.
Telnet, LDAPRemote login to older devices; directory look-ups and sign-inNoLDAP is encrypted with LDAPS or StartTLS. Telnet has no option, so passwords travel in clear text.
TLS, SSHRemote access, cloud historians, and IT systems that reach into OTYes, encrypted. The classical key exchange could be broken by a large enough quantum computer.A hybrid post-quantum key exchange. Recent OpenSSH uses one by default.
IPsec (IKEv2)VPNs and site-to-site connectionsYes, encrypted. The key exchange is classical unless post-quantum extensions are in use.Post-quantum key exchange extensions, when in use.

See a real CBOM excerpt

Coverage

What ClaveQ reports for each connection.

For each connection, ClaveQ gives one of three results: protected, unprotected, or not observed. It marks a connection not observed when ClaveQ never sees its cryptography, for example because the traffic starts mid-session, runs one way only, or uses a protocol ClaveQ does not decode. ClaveQ's decoders are tested on laboratory, public and synthetic traffic, GE-SRTP on synthetic test data only, and none has yet been run on a recording from a customer site. The protocol-by-protocol list is available when you request early access.

Request early access

How it connects

Start with one mirror port. Nothing installed on your control devices.

ClaveQ listens to a copy of the traffic from a mirror (SPAN) port on an existing switch, or a network TAP. It never transmits onto the network it is monitoring, never decrypts, and never touches the devices it is assessing.

IT / EXTERNAL DMZ Level 3.5 Level 3 operations Level 2 supervisory Level 1 control Cloud service Corporate IT IT/OT firewalls · DMZ Historian replica FW via IT/OT firewall Historian to DMZ replica · TLS 1.3 hybrid · quantum-safe SCADA ↔ historian · OPC UA · quantum-vulnerable (logical flow) SCADA (duty / standby) Engineering workstation OT site switch Modbus/TCP · unencrypted S7comm · unencrypted PLC A PLC B Telemetry router DNP3 · unencrypted telemetry WAN (radio / cellular) Outstation RTU (remote site) mirror port one-way copy ClaveQ receive-only capture port never transmits onto this network no agents on devices
An example site. ClaveQ receives a one-way copy of the traffic from a mirror port or network TAP. A mirror port sees only the traffic that passes through that switch; traffic that stays on a cabinet switch or ring needs its own capture point. Start with one and add more where you need them. ClaveQ installs nothing on the PLCs, RTU, HMIs or servers. Levels follow the Purdue model, the standard way of layering a control network; the DMZ is the buffer zone between IT and OT. Ratings shown are illustrative.

Listen First, our practical guide to starting OT security discovery, is free with a work email.

Private beta

We are opening early access to a small number of critical national infrastructure operators.

If you run operational technology in water, energy, healthcare or manufacturing and want an early look, we would like to hear from you.

Thanks — we will be in touch within a couple of days.